Regency Logo

Regency Generators Knowledge Base

How to configure the Start Up Cranking attempts on the DSE 7320 Mk2?

Before you can change anything you must download the DSE Configuration Suite.

Firstly Select the Engine Options tab in the drop down menu.

Here you will find Start Attempts. The number of starting attempts the module makes can be configured to the user requirement. If the module does not detect that the engine has fired before the end of the Cranking Time, then the current start attempt is cancelled and the Crank Rest time takes place before the next crank attempt begins. If, after all configured start attempts, the engine is not detected as running, the Fail to Start shut down alarm is generated.